Analytical modelling and optimisation of a solar-driven cooling system enhanced with a photovoltaic evaporative chimney


Thumbnail

View/Open:
 2024 ATE 245.pdf

2,63 MB
Adobe PDF
Share:
Title:
Analytical modelling and optimisation of a solar-driven cooling system enhanced with a photovoltaic evaporative chimney
Authors:
Ruiz Ramírez, Javier  
Martínez, Pedro Juan
Aguilar-Valero, Francisco Javier  
Lucas Miralles, Manuel  
Editor:
Elsevier
Department:
Departamentos de la UMH::Ingeniería Mecánica y Energía
Issue Date:
2024
URI:
https://hdl.handle.net/11000/35397
Abstract:
Solar-driven heat pump systems can significantly reduce the energy use in buildings, thereby contributing to meet Europe’s climate commitments, including building decarbonisation by 2050. The research gap filled by this study is the development of an analytical model of a novel photovoltaic evaporative cooling chimney system previously described in the literature. The models for the system components were validated with experimental data, showing a maximum difference of 5.83%. An optimisation analysis based on the grid energy efficiency ratio as key performance indicator was conducted. The condenser water flow rate was identified as the key variable in this analysis. For a given design environmental and operating conditions, the optimal value for this magnitude was 1.05 m h−1, enabling a 3.8 kW load with only 44.33 W from the grid. The ambient temperature and relative humidity have the greatest influence on the overall system performance. They affect both, the panels’ efficiency and the chiller performance. Their combined influence could lead to a 10.86% reduction in the energy use while meeting the cooling load. The comparative study considering other solar cooling systems, assessed that the use of the solar chimney and the water–water heat pump enhances the overall performance of the main components of the system: 53% improvement for the chiller and 10% for the PV panels. Both effects combined, lead to an average grid energy efficiency ratio of 11.58. This study provides valuable insights for the design and implementation of efficient solar-driven cooling technologies, advancing beyond previous efforts in the literature.
Keywords/Subjects:
Solar cooling
Solar chimney
Evaporative cooling
HVAC
Knowledge area:
CDU: Ciencias aplicadas: Ingeniería. Tecnología: Ingeniería mecánica en general. Tecnología nuclear. Electrotecnia. Maquinaria
Type of document:
info:eu-repo/semantics/article
Access rights:
info:eu-repo/semantics/openAccess
Attribution-NonCommercial-NoDerivatives 4.0 Internacional
DOI:
https://doi.org/10.1016/j.applthermaleng.2024.122878
Appears in Collections:
Artículos Ingeniería Mecánica y Energía



Creative Commons ???jsp.display-item.text9???